Greenpower_c.mit
05/Nov/2010

Contents:




Project summary
Building
History
#TotalHeatingCoolingFans/PumpsLightsEquip.
run123120037
Model data:
Project file
Greenpower_c.mit
Building floor area
319.79 m2
Total volume
1429.91 m3
Calculation data:
Results file
"c:\..\vista\greenpower_c.aps"
Calculated
05/Nov/2010 on 01:00
Calc. Period:
01/Jan - 31/Dec
Weather:
Climate file
SouthamptonDSY05.fwt
Note: The results in this report are generated by the IES ApacheSim module. ApacheSim is a rigorous building thermal simulation approach that conforms to ANSI/ASHRAE Standard 140. If you wish to know more about ApacheSim and obtain a copy of the ANSI/ASHRAE 140 standard report select the following link (will open new window) www.iesve.com/apachesim
Building systems energy
Summary
MonthHeating
(boilers etc.)
Cooling
(chillers etc.)
Fans, pumps and controlsLightsEquip.
A-ZHi/LoHi/LoHi/LoHi/LoHi/Lo
Jan3.40.00.00.30.6
Feb2.60.00.00.30.5
Mar1.40.00.00.30.6
Apr0.50.00.00.30.5
May0.20.00.00.30.6
Jun0.00.00.00.30.5
Jul0.00.00.00.30.6
Aug0.00.00.00.30.6
Sep0.10.00.00.30.5
Oct0.60.00.00.30.6
Nov1.40.00.00.30.5
Dec2.60.00.00.30.5
Total12.80.00.43.36.5
Copyright © 2009 Integrated Environmental Solutions Limited All rights reserved
MWh
The maximum value in each column is highlighted in red. The minimum value in each column is highlighted in blue.
More than one value
may be highlighted
Total Yearly Energy Consumption = 23.0MWh
Total Yearly Energy Consumption per Floor Area = 72.1kW/m2
Carbon Dioxide
Summary
MonthSystem
(boilers, chillers, fans,pumps)
LightsEquip.
A-ZHi/LoHi/LoHi/Lo
Jan697.0150.6296.9
Feb528.6130.9258.3
Mar298.4144.0284.1
Apr109.1137.5271.2
May50.7150.6296.9
Jun22.1137.5271.2
Jul21.7144.0284.1
Aug23.5150.6296.9
Sep30.5130.9258.4
Oct139.8150.6296.9
Nov294.0144.0284.0
Dec540.0137.5271.3
Total2,755.41,708.53,370.3
Copyright © 2009 Integrated Environmental Solutions Limited All rights reserved
kgCO2
The maximum value in each column is highlighted in red. The minimum value in each column is highlighted in blue.
More than one value
may be highlighted
Total carbon dioxide emissions = 7,834.2kgCO2
Comfort - Occupied
Occupied
TempRelative HumidityPPD
Room NameMax
°C
Min
°C
Max
%
Min
%
Max
%
Min
%
A-ZHi/LoHi/LoHi/LoHi/LoHi/LoHi/Lo
Level 0 Lecture space29.220.079.523.656.85.0
Level 0 Store - - - - - -
Level 0 Office/Workshop/Storage (double height)29.520.074.019.466.45.0
Level 1 Office/Workshop/Storage (double height)31.020.072.119.679.05.0
Stack - - - - - -
Stack - - - - - -
Level 0 Toilet female27.511.874.222.471.25.0
Level 0 plant - - - - - -
Level 0 Toilet disabled27.411.773.021.672.15.0
Level 0 Toilet male27.112.374.522.766.55.0
Level 0 Toilet lobby27.611.271.719.976.55.0
Copyright © 2009 Integrated Environmental Solutions Limited All rights reserved
PPD is the percentage of people that will
find the room thermally uncomfortable

Please alter the PPD max limit value to
highlight rooms that are more
thermally uncomfortable

(US Only)ASHRAE 55 states comfort
lies between 5 and 10% PPD
Comfort - Full Day
Full Day
TempRelative HumidityPPD
om NameMax
°C
Min
°C
Max
%
Min
%
Max
%
Min
%
A-ZHi/LoHi/LoHi/LoHi/LoHi/LoHi/Lo
Level 0 Lecture space29.28.379.520.592.75.0
Level 0 Store30.07.878.019.995.45.0
Level 0 Office/Workshop/Storage (double height)29.57.778.419.495.65.0
Level 1 Office/Workshop/Storage (double height)31.07.678.719.696.85.0
Stack29.8-0.3100.027.9100.05.0
Stack29.8-0.3100.027.3100.05.0
Level 0 Toilet female27.511.774.220.772.05.0
Level 0 plant26.811.471.119.575.35.0
Level 0 Toilet disabled27.411.673.019.872.45.0
Level 0 Toilet male27.112.274.520.267.35.0
Level 0 Toilet lobby27.611.271.719.976.55.0
Copyright © 2009 Integrated Environmental Solutions Limited All rights reserved
PPD is the percentage of people that will
find the room thermally uncomfortable

Please alter the PPD max limit value to
highlight rooms that are more
thermally uncomfortable

(US Only)ASHRAE 55 states comfort
lies between 5 and 10% PPD
Peak Hourly Room Loads
Peak Loads
Peak Room Conditioning Loads (kW)Internal Gains*Cooling Checks
Room NameSensible
Heating
Sensible
Cooling
Humidi-
fication
Dehumid-
ification
(kW)(W/m2)(l/(s•m2))
A-ZHi/LoHi/LoHi/LoHi/LoHi/LoHi/LoHi/Lo
Level 0 Lecture space6.43000.90320.00000.36921.248819.141.98
Level 0 Store0.0000-0.00000.0000-0.00000.0001n/an/a
Level 0 Office/Workshop/Storage (double height)25.72872.75050.47500.66393.681417.601.82
Level 1 Office/Workshop/Storage (double height)20.93491.37890.21910.36951.679419.342.00
Stack0.0000-0.00000.0000-0.00000.0000n/an/a
Stack0.0000-0.00000.0000-0.00000.0000n/an/a
Level 0 Toilet female1.5041-0.00000.0000-0.00000.0492n/an/a
Level 0 plant0.0000-0.00000.0000-0.00000.0000n/an/a
Level 0 Toilet disabled1.3029-0.00000.0000-0.00000.0361n/an/a
Level 0 Toilet male1.6908-0.00000.0000-0.00000.0573n/an/a
Level 0 Toilet lobby0.8404-0.00000.0000-0.00000.0108n/an/a
Copyright © 2009 Integrated Environmental Solutions Limited All rights reserved
Recommended strategies to reduce the loads on these rooms are:
- reorient the building
- move rooms with high internal gain to avoid solar penetration
- increase u-values of constructions
- improve solar performance of the glazing